The AW-CFP2166 1 Zone series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
The AW-CFP2166 series 1 Zone conventional fire alarm panel is the heart of the conventional fire alarm system, which can realize centralized control, can supply power to the detectors.
AC INPUT | 220VAC 50/60Hz | +10% |
-15% | ||
DC OUTPUT | 24VDC typical | |
Voltage for MCU | 5V | |
Current @ 220VAC | standby current ≤250mA | |
Maximum current | 1A | |
Batteries current | 750mA maximum, current limited | |
Batteries | 2*12V/ 2.3Ah sealed lead acid gel, self-regulated | |
Battery low-voltage protection | 22.2V | |
The maximum and minimum electrical ratings for each input and output | Detectots / zone lines: 21V-26V Sounder1 and sounder2 lines:21-26.2V Fire protection/Fire routing/Fault routing lines:21-26.2V | |
Max points (detector and MCP) per CIE | 20 detectors and 10 MCPs | |
Zone alarm current | 6mA minimum/ 27mA maximum | |
Sounder output | 2*0.3A maximum | |
Relay contacts rating | Dry contacts (NO/NC) 1A @24VDC | |
EOL resistor for zone and outputs | 6.8K 1W | |
Fuse on EMI board | 2A/ 250V Ceramic slow blow fuse 5*20(mm) | |
Environmental | Class A temperature range: -5 to 40°C (23~104°F) Humidity: 5 to 95% RH, non-condensing | |
Terminal blocks rating | All terminals rated for 12 to18 AWG (0.75 to 2.5 mm2) | |
Service life | 10 years |