LPCB Addressable Fire Alarm System Input Output Module Feature:
1. Executive standard: EN54-18
2. Operation voltage: loop DC24V (polarity-insensitive);power DC24V(polarity-insensitive)
3. Quiescent current: loop current<0.8mA; power current<2mA
4. Action current: loop current<5mA; power current<15mA
5. Capacity of the output control contact: 1A@DC30V
6. Operation indicator: The inspection indicator will blink once about every 12 seconds in the inspection status or remain lit in
the output status; the input indicator will remain lit in the feedback status.
7. Operating environment: Temperature: -10ºC ~ 55ºC; RH: ≤95% (40 ºC±2ºC, without condensation)
8. External dimensions: 86×86×41(mm,With base)
9. Weight: about 148g(With base)