4 Zone Fire Alarm Control Panel AW-CFP2166-4-8

And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations, and sprinkler supervision. Each zone can be disabled by a button. The basic unit offers 1 to 8 zones of initiation, up to 16 zones for larger applications.

Product Price
Rp1
Quantity

And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations, and sprinkler supervision. Each zone can be disabled by a button. The basic unit offers 1 to 8 zones of initiation, up to 16 zones for larger applications.

4 Zone Fire Alarm Control Panel Specification
1. It is modularized design, the panel can expend from 1 zone to 32 zones easily.
2. It has 2 level control mode by a lock
3. It has 24VDC and 5VDC power supply output.
4. It has FIRE and FAULT signal output.
5. It has 2 general sounders output.
6. Each zone has 1 circuit detectors input
7. Each zone can be disable by a button.
8. It has RESET button to reset the panel.
9. It has SILENCE button to stop BUZZER and SOUNDERS.
10. It has EVACUATE button to start a manual fire alarm immediately.
11. It has battery low protection function, when battery voltage lower than 21VDC
battery will be cut off automatically until the mains power is on.
12. It has an optional GSM module for fire alarm by SMS


AC INPUT
 
220VAC 50HZ
+10%
  -15%
DC OUTPUT24VDC typical
Voltage for MCU5V for power board MCU, 3.3V for others
Current at 24VDC from PSE450mA standby current
Maximum current from PSE2A except batteries charge
Batteries current1.85A maximum, current limited
 
Auxiliary output
24VDC +/- 10%, 100 mA max,
current limited, monitored
 
Batteries
2*12V/ 2.3Ah sealed lead acid gel,
self-regulated
 2*12V/ 7Ah if needed
Battery replace Resistance2Ω±10% if needed
Battery low-voltage protection22.2V
Detectors connection allowed each zone20 (except MCPs)
Zone alarm current6mA minimum/ 27mA maximum
Sounder output2*0.75A maximum
Fire protection100mA maximum
Fire routing100mA maximum
Fault routing100mA maximum
Communication protocol2 wires RS485 bus system
Relay contacts ratingDry contacts (NO/NC) 1A @24VDC
EOL resistor for zone6.8K 1W
EOL resistor for outputs6.8K 1W
Fuse on power board3A/ 250V glass tube fuse 20mm
Fuse on EMI board1A/ 250V glass tube fuse 20mm
 
Environmental
Class A temperature range: -5 to 40°C (23~104°F)
Humidity: 5 to 95% RH, non-condensing
 
Terminal blocks rating
All terminals rated for 12 to18 AWG
(0.75 to 2.5 mm2)